Following please find the description for the attached Revision 3 drawing sheet updates for the addition of millwork slat components and logo panel at Reception 1900. The following adjustments occurred in response to an RFI. MECHANICAL 1. Existing and new fire dampers were adjusted to accurately reflect site conditions and follow code requirements. Neither the tenant demising walls nor the walls between the tenants and corridors need fire dampers. 2. Sound attenuation transfer duct detail was added to sheet TM19.0. 3. Keynote 5 was modified to state, “Verify existing transfer does not have sound attenuation boot. If existing transfer has sound attenuation boot, existing transfer and associated boot are existing to remain. If existing transfer does not have sound attenuation boot, provide sound attenuation boot equivalent in size to existing transfer. Refer to sound attenuation transfer duct detail.” a. Keynote 5 was placed next to the existing transfer on the plan North tenant demising wall. 4. Keynote 9 now states, “Note no longer utilized.” a. All references of keynote 9 on plan have been removed.